Heliotherm heat pump parameters

Tested with:

  • Heliotherm HP08S10W-WEB, SW 3.0.20
  • Heliotherm HP10S12W-WEB, SW 3.0.8
  • Heliotherm HP08E-K-BC, SW 3.0.7B
  • Heliotherm HP05S07W-WEB, SW 3.0.17 and SW 3.0.37
  • Heliotherm HP12L-M-BC, SW 3.0.21
  • Heliotherm HP-30-L-M-WEB, SW 3.0.21

SP Data Points

Parameter Name Data Point ACL Data Type Min Value Max Value
Liegenschaft SP,NR=3 r- INT 0 2147483647
WP_System SP,NR=4 r- INT 1 2
WW Type SP,NR=5 r- INT 0 4
FWS Type SP,NR=6 r- BOOL 0 1
Puffer Type SP,NR=7 r- BOOL 0 1
Softwareversion SP,NR=9 r- INT 0 0
Verdichter_Status SP,NR=10 r- INT 0 11
Verdichter laeuft seit SP,NR=11 r- INT 10 100000
Verdichter Einschaltverz.(sec) SP,NR=12 r- INT 0 10800
Betriebsart [1] SP,NR=13 r- INT 0 7
HKR Soll_Raum SP,NR=69 r- FLOAT 10.0 25.0
HKR Aufheiztemp. (K) SP,NR=71 r- INT 1 10
HKR Absenktemp. (K) SP,NR=72 r- INT -10 -1
HKR Heizgrenze SP,NR=76 r- INT 0 45
HKR RLT Soll_oHG (Heizkurve) SP,NR=80 r- FLOAT 15.0 40.0
HKR RLT Soll_0 (Heizkurve) SP,NR=81 r- FLOAT 20.0 50.0
HKR RLT Soll_uHG (Heizkurve) SP,NR=82 r- FLOAT 25.0 60.0
WW Normaltemp. SP,NR=83 r- INT 10 75
WW Hysterese Normaltemp. SP,NR=84 r- INT 1 10
WW Minimaltemp. SP,NR=85 r- INT 5 45
WW Hysterese Minimaltemp. SP,NR=86 r- INT 1 10
BSZ HKP Betriebsstunden SP,NR=153 r- INT 0 100000
BSZ HKP Schaltung SP,NR=155 r- INT 0 100000
BSZ EQ Betriebsstunden SP,NR=162 r- INT 0 100000
BSZ EQ Schaltungen SP,NR=164 r- INT 0 100000
BSZ WWV Betriebsstunden SP,NR=165 r- INT 0 100000
BSZ WWV Schaltungen SP,NR=167 r- INT 0 100000
BSZ ZIPWW Betriebsstunden SP,NR=168 r- INT 0 100000
BSZ ZIPWW Schaltungen SP,NR=170 r- INT 0 100000
BSZ Verdichter Betriebsst. WW SP,NR=171 r- INT 0 100000
BSZ Verdichter Betriebsst. HKR SP,NR=172 r- INT 0 100000
BSZ Verdichter Betriebsst. ges SP,NR=173 r- INT 0 100000
BSZ Verdichter akt. Laufzeit SP,NR=174 r- INT 0 100000
MKR2 Aktiviert SP,NR=222 r- INT 0 2
Energiezaehler SP,NR=263 r- INT 0 2
BSZ Verdichter Schaltung WW SP,NR=375 r- INT 0 100000
[1]

Betriebsart:

  • 0 = Aus
  • 1 = Automatik
  • 2 = Kühlen
  • 3 = Sommer
  • 4 = Dauerbetrieb
  • 5 = Absenkung
  • 6 = Urlaub
  • 7 = Party
  • [8 = Ausheizen]
  • [9 = EVU-Sperre]
  • [10 = Hauptschalter]

MP Data Points

Parameter Name Data Point ACL Data Type Min Value Max Value
Temp. Aussen MP,NR=0 r- FLOAT -20.0 40.0
Temp. Aussen verzoegert MP,NR=1 r- FLOAT -20.0 40.0
Temp. Brauchwasser MP,NR=2 r- FLOAT 0.0 70.0
Temp. Vorlauf MP,NR=3 r- FLOAT 0.0 70.0
Temp. Ruecklauf MP,NR=4 r- FLOAT 0.0 70.0
Temp. Pufferspeicher MP,NR=5 r- FLOAT 0.0 70.0
Temp. EQ_Eintritt MP,NR=6 r- FLOAT -20.0 30.0
Temp. EQ_Austritt MP,NR=7 r- FLOAT -20.0 30.0
Temp. Sauggas MP,NR=9 r- FLOAT -20.0 30.0
Temp. Frischwasser_Istwert MP,NR=11 r- FLOAT 0.0 70.0
Temp. Verdampfung MP,NR=12 r- FLOAT -50.0 30.0
Temp. Kondensation MP,NR=13 r- FLOAT -50.0 60.0
Temp. Heissgas MP,NR=15 r- FLOAT 0.0 150.0
Niederdruck (bar) MP,NR=20 r- FLOAT 0.0 18.0
Hochdruck (bar) MP,NR=21 r- FLOAT 0.0 40.0
Heizkreispumpe MP,NR=22 r- BOOL False True
EQ Pumpe (Ventilator) MP,NR=24 r- BOOL False True
Warmwasservorrang MP,NR=25 r- BOOL False True
Zirkulationspumpe WW MP,NR=29 r- BOOL False True
Verdichter MP,NR=30 r- BOOL False True
Stoerung MP,NR=31 r- BOOL False True
Hauptschalter MP,NR=36 r- BOOL False True
FWS Stroemungsschalter MP,NR=38 r- BOOL False True
BSZ Verdichter Schaltungen MP,NR=41 r- INT 0 100000
Frischwasserpumpe MP,NR=50 r- INT 0 100
Verdichteranforderung MP,NR=56 r- INT 0 5
HKR_Sollwert MP,NR=57 r- FLOAT 0.0 50.0